Zoning FAQs
|
| Step | Action | Check(s) |
| 1 | Turn off power to zone panel and remove cover. | |
| 2 | Verify E-Heat switch is in off position, and DIP switches are set properly. The zone panel will not cool if E-Heat is switched on. |
J |
| 3 | Ensure supply temp sensor is wired to terminals SA1 and SA2. Dampers will not close and the zone panel will not stage if the SAS is missing or damaged |
D |
| 4 | Ensure no zones are calling by turning all thermostats off. | |
| 5 | Apply 24 VAC Power to the 140303 3 Zone panel. | |
| 6 | Verify green power LED near 24 VAC Terminals is lit. | A |
| 7 | Verify green heartbeat LED in middle of panel is pulsing. | A-B-H-K |
| 8 | Verify all 3 zone LED's near damper terminals are green. | A-B-C |
| 9 | Verify Supply temp display shows current plenum temperature. | D |
| 10 | Switch zone 1 thermostat to heat mode, and call for heat in zone 1. | |
| 11 | Verify zone 1 damper LED stays green (open) and zone 2 and 3 damper LEDs change to red (closed). |
E-F |
| 12 | Verify heating system is operating, air is moving out zone 1 vents, and zone 2 and 3 vents have minimal airflow. |
F-G |
| 13 | Verify supply temp display measures heat change in supply air. Switch zone 2 thermostat to heat mode, and call for heat in zone 2 by raising set temperature above room temperature. |
D |
| 14 | Verify zone 1 damper LED stays green (open) and zone 2 damper LED changes to green (open). |
E |
| 15 | Verify heating system is operating and air is moving out into zone 1 and zone 2. | E-F-G |
| 16 | If installed, switch zone 3 thermostat to heat mode, and call for heat in zone 3. | |
| 17 | Verify air is now flowing to zone 3. | E-F-G |
| 18 | Return zone 1 thermostat to the off position. Verify zone 1 damper LED turns red and zone 2 and 3 damper LEDs stay green. |
E-F-G |
| 19 | Verify heating system is operating, air is moving out zone 2 and 3 vents, and zone 1 vents have minimal airflow. |
E-F-G |
| 20 | Return zone 2 and 3 thermostats to the off position. Verify system fan shuts off at the end of purge cycle. |
H |
| 21 | Verify all zone LED's near damper terminals are green. | E-F-G-H |
| 22 | If the outside temperature is acceptable, repeat the above steps in cooling mode. Cooling will not work if E-Heat is on. |
|
| 23 | When checkout is finished, restore thermostats and retest entire system. | |
| 24 | If the above steps do not solve the problem, please contact Braeburn Technical Support at techsupport@braeburnonline.com or the numbers listed below. |
|
2 Zone Panel Troubleshooting Steps |
|
Step |
Action |
Check(s) |
1 |
Turn off power to zone panel and remove cover. |
|
2 |
Verify E-Heat switch is in off position, and DIP switches are set properly. |
J |
3 |
Ensure no zones are calling by turning all thermostats off. |
|
4 |
Apply 24 VAC Power to the 140202 2 Zone panel. |
A |
5 |
Verify green power LED near 24 VAC Terminals is lit. |
A |
6 |
Verify green heartbeat LED in middle of panel is pulsing. |
A-B-H |
7 |
Verify both zone LED's near damper terminals are green. |
A-B-C |
8 |
Switch zone 1 thermostat to heat mode, and call for heat in zone 1. |
|
9 |
Verify zone 1 damper LED is green (open) and zone 2 damper LED is red. |
E-F |
10 |
Verify heating system is operating, air is moving out zone 1 vents, and zone 2 vents have minimal airflow. |
F-G |
11 |
Verify supply temp display measures heat change in supply air. Switch zone 2 thermostat to heat mode, and call for heat in zone 2 by raising set temperature above room temperature. |
D |
12 |
Verify zone 1 damper LED stays green (open) and zone 2 damper is green |
E |
13 |
Verify heating system is operating and air is moving out into zone 1 and 2. |
E-F-G |
14 |
Return zone 1 thermostat to the off position. Verify zone 1 damper LED turns red and zone 2 damper LED stay green. |
E-F-G |
15 |
Verify heating system is operating, air is moving out zone 2 vents, and zone 1 vents have minimal airflow. |
E-F-G |
16 |
Turn zone 2 off. Verify system fan shuts off at the end of purge cycle. |
H |
17 |
Verify all zone LED's near damper terminals are green. |
E-F-G-H |
18 |
If the outside temperature is acceptable, repeat the above steps in cooling mode. Cooling will not work if E-Heat is on. |
|
19 |
When checkout is finished, restore thermostats and retest entire system. |
|
20 |
If the above steps do not solve the problem, please contact Braeburn Technical Support at techsupport@braeburnonline.com or the numbers listed below. |
|
|
Zone System Checks |
Solution |
Action |
A |
Check zonepaneltransformeroutputfor 24VAC,verifytransformerinput power |
B |
Mark and removeallwires exceptpower toverify no wiring shorts exist |
C |
Turn allthermostats OFF |
D |
Turn off power and check resistance at terminals SAS1, SAS2, Sensor should read 1K to 10K |
E |
Mark and removethermostat wiring. Use jumpers to verify thermostatoperation |
F |
Mark and removedamper wiring.Check for damperwiring shorts and opens |
G |
Mark and remove damper wiring. Verify damper operation by powering damper directly from24VACsource |
H |
Possible defectivepanel. Consultfactory for technical support |
J |
Download manual or refer to zonepanelinside coverforDIP switchsetting |
K |
Verifyvoltageinput to panel. Voltageinputmustbe between 21 and 29 VAC |